Skip to main content

Table 7 Comparison of results for IEEE 69-bus system with two DG units

From: A new optimal allocation of DGs in distribution networks by using coot bird optimization method

Method

Size (MW)

Location

PF

Total real power loss (kW)

Loss reduction (%)

GA (Shukla et al. 2010)

0.555

11

1

71.7912

68.08

1.777

61

1

GA (Pisica et al. 2009)

0.006

1

1

84.233

62.55

1.794

62

1

CSA (Shukla et al. 2010)

0.6

22

1

76.4

66

2.1

61

1

PSO (Shukla et al. 2010)

0.7

14

1

78.8

64.97

2.1

62

1

MTLBO (García and Mena 2013)

0.52

17

1

71.776

68.09

1.732

61

1

LSM (Kollu et al. 2014)

0.4461

27

1

100.39

55.38

1.3791

65

1

AGA (Ganguly and Samajpati 2017)

0.389

18

1

72.763

67.66

1.848

61

1

SFS (Nguyen and Vo 2019)

0.531

17

1

71.68

68.14

1.781

61

1

CSFS3 (Nguyen and Vo 2019)

0.531

17

1

71.68

68.14

1.781

61

1

CBOM

0.531

17

1

71.677

68.144

1.781

61

1

ALOA (Ali et al. 2017)

0.603

17

0.83

20.9342

90.69

1.2

61

0.8

CBOM

0.522

17

0.828

7.204

96.798

1.735

61

0.814