Skip to main content

Table 6 Comparison of results for IEEE 69-bus system with one DG unit

From: A new optimal allocation of DGs in distribution networks by using coot bird optimization method

Method

Size (MW)

PF

Location

Total real power loss (kW)

Loss reduction (%)

ABC (Abu-Mouti and El-Hawary 2011)

1.9

1

61

83.31

62.96

GA (Hassan et al. 2017)

1.872

1

61

83.18

63.02

Analytical (Gözel and Hocaoglu 2009)

1.808

1

61

92

59.1

GA (Pisica et al. 2009)

1.794

1

61

83.43

62.91

CSA (Tan et al. 2012)

2

1

61

83.8

62.74

SGA (Tan et al. 2012)

2.3

1

61

89.4

60.3

PSO (Tan et al. 2012)

2

1

61

83.8

62.75

MTLBO (García and Mena 2013)

1.82

1

61

83.323

62.95

BB-BC (Abdelaziz et al. 2015)

1.873

1

61

83.225

63

SFS (Nguyen and Vo 2019)

1.873

1

61

83.22

63.01

CSFS3 (Nguyen and Vo 2019)

1.873

1

61

83.22

63.01

CBOM

1.873

1

61

83.22

63.01

BB-BC (Abdelaziz et al. 2015)

1.801

0.81

61

23.1737

89.697

ALOA (Ali et al. 2017)

1.827

0.82

61

23.1925

89.69202

CBOM

1.828  

0.8149

61

23.17

89.702