Skip to main content

Table 5 IEEE 69 bus distribution system results

From: A new optimal allocation of DGs in distribution networks by using coot bird optimization method

Number of DG

Location

Size (kW)

PF

Total DG Size (kW)

Total real power loss (MW)

Loss reduction (%)

Minimum bus voltage @bus

Without DG

–

–

–

–

0.225

0

0.9092 @65

One DG

61

1872.689

1

1872.689

0.083224

63.012

0.9683 @27

61

1828.451

0.814874

1828.451

0.02317

89.702

0.9725 @27

Two DG

17

531.4872

1

2773.4872

0.071677

68.144

0.9789 @65

61

1781.461

1

17

522.3443

0.828229

2257.0243

0.007204

96.798

0.9943 @50

61

1734.68

0.813865

Three DG

11

526.8575

1

2626.1658

0.069428

69.143

0.9790 @65

18

380.3413

1

61

1718.967

1

11

537.029

0.831323

2556.6919

0.004277

98.099

0.9943 @50

21

346.5029

0.83261

61

1673.16

0.81302