Skip to main content

Table 1 IEEE 33 bus distribution system results

From: A new optimal allocation of DGs in distribution networks by using coot bird optimization method

Number of DG

Location

Size (kW)

PF

Total DG Size (kW)

Total real power loss (MW)

Loss reduction (%)

Minimum bus voltage @bus

Without DG

–

–

–

–

0.21099

0

0.9131 @18

One DG

6

2575.315

1

2575.315

0.10397

50.723

0.9511 @18

26

2410.084

0.819644

2410.084

0.062466

70.394

0.9643 @18

Two DG

13

851.5087

1

2009.1407

0.087167

58.687

0.9685 @33

30

1157.632

1

13

819.6654

0.884545

2062.7914

0.029312

86.107

0.9804 @25

30

1243.126

0.8

Three DG

13

801.7063

1

2946.6753

0.072787

65.502

0.9687 @33

24

1091.329

1

30

1053.64

1

14

739.0424

0.882467

2944.4054

0.012744

93.96

0.9916 @8

24

1048.879

0.883921

30

1156.484

0.8