From: A model-based approach for converting CGMES power system models into operational networks
CGMES model | Pandapower model | ||
---|---|---|---|
Classes | Properties | Parameters | Element |
External-Network-Injection | id | id | External Grid |
IdentifiedObject.name | name | ||
ExternalNetworkInjection.p | p_mw | ||
ExternalNetworkInjection.minQ | min_q_mvar | ||
ExternalNetworkInjection.maxQ | max_q_mvar | ||
ExternalNetworkInjection.minP | min_p_mw | ||
ExternalNetworkInjection.maxP | max_p_mw | ||
ExternalNetworkInjection.maxInitialSymShCCurrent | s_sc_max_mva | ||
ExternalNetworkInjection.minInitialSymShCCurrent | s_sc_min_mva | ||
ExternalNetworkInjection.minR1ToX1Ratio | rx_min | ||
ExternalNetworkInjection.maxR1ToX1Ratio | rx_max | ||
ExternalNetworkInjection.maxZ0ToZ1Ratio | x0x_max | ||
ExternalNetworkInjection.maxR0ToX0Ratio | r0x0_max | ||
SvStatus | SvStatus.inService | in_service |