Table 3 Excerpt from the numerical results for node phase-to-phase voltage magnitude and angle regarding the medium-voltage benchmark grid

From: CIMverter–a template-based flexibly extensible open-source converter from CIM to Modelica

Grid NEPLAN ModPowerSystems PowerSystems
Node |V| [kV] V[] |V| [kV] V[] |V| [kV] V[]
N 0 110.000 0.000 110.000 0.000 110.000 0.000
N 1 19.531 -4.300 19.532 -4.268 19.532 -4.268
N 10 18.828 -4.900 18.828 -4.852 18.828 -4.852
N 11 18.825 -4.900 18.826 -4.852 18.826 -4.852
  1. The models based on the ModPowerSystems and PowerSystems libraries yield equal results using the Dymola environment and dassl solver. The results deviate mariginally from the reference results obtained with the proprietary tool NEPLAN, which might be explained by numerical rounding and different solution methods