Table 1 Hysteresis parameters for conventional operation strategy (Panten 2019)

From: Comparative study of algorithms for optimized control of industrial energy supply systems

System Switch-on condition Switch-off condition
CHP THS,t<72C ¬(THS,t<86CTHS,b<69C)
B THS,t<71C ¬(THS,t<85CTHS,b<68C)
IH THS,t<70C ¬(THS,t<83CTHS,b<67C)
CC TCS,b>16C ¬(TCS,b>6CTCS,t>16C)
CT TCS,b>15C ¬(TCS,b>5CTCS,t>15C)
HP \(\begin {array}{l}\left (T_{\text {HS},\mathrm {t}}<70,5^{\circ }C \vee T_{\text {CS}, \mathrm {b}}>16,5^{\circ }\mathrm {C}\right) \ldots \wedge T_{\text {HS},\mathrm {t}}<84^{\circ }C\wedge T_{\text {CS}, \mathrm {b}}>7^{\circ }\mathrm {C}\end {array}\) \(\begin {array}{l}\neg \left (\left (T_{\text {HS}, \mathrm {t}}<84^{\circ }C \wedge T_{\text {CS}, \mathrm {b}}>7^{\circ }C\right) \ldots \wedge \left (T_{\text {HS}, \mathrm {b}}<70^{\circ }C \vee T_{\text {CS}, \mathrm {t}}>16,5^{\circ }\mathrm {C}\right)\right) \end {array}\)
  1. ¬ (not), (and), (or)