From: Comparative study of algorithms for optimized control of industrial energy supply systems
System | Switch-on condition | Switch-off condition |
---|---|---|
CHP | THS,t<72∘C | ¬(THS,t<86∘C∧THS,b<69∘C) |
B | THS,t<71∘C | ¬(THS,t<85∘C∧THS,b<68∘C) |
IH | THS,t<70∘C | ¬(THS,t<83∘C∧THS,b<67∘C) |
CC | TCS,b>16∘C | ¬(TCS,b>6∘C∧TCS,t>16∘C) |
CT | TCS,b>15∘C | ¬(TCS,b>5∘C∧TCS,t>15∘C) |
HP | \(\begin {array}{l}\left (T_{\text {HS},\mathrm {t}}<70,5^{\circ }C \vee T_{\text {CS}, \mathrm {b}}>16,5^{\circ }\mathrm {C}\right) \ldots \wedge T_{\text {HS},\mathrm {t}}<84^{\circ }C\wedge T_{\text {CS}, \mathrm {b}}>7^{\circ }\mathrm {C}\end {array}\) | \(\begin {array}{l}\neg \left (\left (T_{\text {HS}, \mathrm {t}}<84^{\circ }C \wedge T_{\text {CS}, \mathrm {b}}>7^{\circ }C\right) \ldots \wedge \left (T_{\text {HS}, \mathrm {b}}<70^{\circ }C \vee T_{\text {CS}, \mathrm {t}}>16,5^{\circ }\mathrm {C}\right)\right) \end {array}\) |