Skip to main content

Table 1 Hysteresis parameters for conventional operation strategy (Panten 2019)

From: Comparative study of algorithms for optimized control of industrial energy supply systems

System

Switch-on condition

Switch-off condition

CHP

THS,t<72∘C

¬(THS,t<86∘C∧THS,b<69∘C)

B

THS,t<71∘C

¬(THS,t<85∘C∧THS,b<68∘C)

IH

THS,t<70∘C

¬(THS,t<83∘C∧THS,b<67∘C)

CC

TCS,b>16∘C

¬(TCS,b>6∘C∧TCS,t>16∘C)

CT

TCS,b>15∘C

¬(TCS,b>5∘C∧TCS,t>15∘C)

HP

\(\begin {array}{l}\left (T_{\text {HS},\mathrm {t}}<70,5^{\circ }C \vee T_{\text {CS}, \mathrm {b}}>16,5^{\circ }\mathrm {C}\right) \ldots \wedge T_{\text {HS},\mathrm {t}}<84^{\circ }C\wedge T_{\text {CS}, \mathrm {b}}>7^{\circ }\mathrm {C}\end {array}\)

\(\begin {array}{l}\neg \left (\left (T_{\text {HS}, \mathrm {t}}<84^{\circ }C \wedge T_{\text {CS}, \mathrm {b}}>7^{\circ }C\right) \ldots \wedge \left (T_{\text {HS}, \mathrm {b}}<70^{\circ }C \vee T_{\text {CS}, \mathrm {t}}>16,5^{\circ }\mathrm {C}\right)\right) \end {array}\)

  1. ¬ (not),∧ (and),∨ (or)