Skip to main content

Table 1 Power Factor - Irish Distribution Code Example

From: Deriving policies from connection codes to ensure ongoing voltage stability

Voltage Range

Connected at:

At 100% Registered Capacity

At 35% of Registered Capacity

99kV ≤V≥ 123kV

110kV

0.93 power factor leading to 0.85 power factor lagging

0.7 power factor leading to 0.4 power factor lagging

85kV ≤V≥ 99kV

110kV

Unity power factor to 0.85 power factor lagging

0.7 power factor leading to 0.4 power factor lagging