Table 3 Characteristics of additional elements of the synthetic distribution network

From: Systematic dynamic assessment for resilient operation of distribution networks

Element

Connection point

Parameter

Value

Wind farms

MV-BB001

Rated Power [MVA]

10.00

  

Rated power factor [-]

0.90

 

MV-BB022

Rated Power [MVA]

5.00

  

Rated power factor [-]

0.90

 

MV-BB047

Rated power [MVA]

5.00

  

Rated power factor [-]

0.90

Shunt reactor

MV-BB001

Rated voltage [kV]

23

  

Number of steps [-]

4

  

Reactive power / step [MVAr]

1.00

HV/MV transformer

HV-BB001 MV-BB001

Rated power [MVA]

25.00

  

Rated Voltage [kV]

110/23

  

Resistance [p.u.]

0.004

  

Reactance [p.u.]

0.01

  

Vector Group

YYn0

  

Tap changer HV side

-12/12; 1.5% V Rate

MV/MV transformer

MV-BB095 MV-BB102

Rated power [MVA]

10.00

  

Rated Voltage [kV]

20/20

  

Resistance [p.u.]

0.006

  

Reactance [p.u.]

0.01

  

Vector Group

YYn0

  

Tap changer MV-BB095 side

-10/10; 1.0% V Rate

External grid

HV-BB001

Short-circuit power [MVA]

1000

  1. Electrical parameters of elements